Three Phase Shunt APF-STATCOM Harmonic, Unbalance Load and Reactive Current Compound Control Strategy in smart Distributed GridJI Xiaochun1, WANG Jianhua2,JI Baojian3, Cai Wu2, JIANG Long1, Zhou Zhong
Abstract: Based on compound power quality concept, this paper proposed a compound harmonic, negative and reactive current compensation strategy for harmonic current, load imbalance and low power factor issues in smart distributed grid. Key factors are presented in detail. Corresponding three phase four line APF-STATCOM simulation and experimental tests and field operation results verify the compound control and compensation concept.
Key words: Smart distributed grid;active power filter(APF); static synchronous compensator(STATCOM);harmonic;unbalanced load;reactive;compound control
摘要:基于電能質(zhì)量復(fù)合控制思想,針對智能配電網(wǎng)中諧波電流、負(fù)載不平衡、功率因數(shù)較低問題,給出一種諧波、負(fù)序及無功電流復(fù)合補(bǔ)償策略,并給出關(guān)鍵參數(shù)設(shè)計(jì)方法。相關(guān)APF-STATCOM仿真、實(shí)驗(yàn)驗(yàn)證及產(chǎn)品現(xiàn)場運(yùn)行實(shí)測結(jié)果驗(yàn)證了復(fù)合控制思想及補(bǔ)償策略正確性及可行性。
關(guān)鍵詞:智能配電網(wǎng);有源電力濾波器;靜止同步補(bǔ)償器;不平衡負(fù)載
近年來,出于節(jié)能環(huán)保的考慮,配電網(wǎng)終端供電系統(tǒng)中電力電子變換裝置應(yīng)用越來越廣泛,如照明、辦公、空調(diào)、電梯等相關(guān)供電系統(tǒng),但這類非線性電能變換裝置在改善用戶端電能質(zhì)量同時(shí),往往誘發(fā)配電網(wǎng)側(cè)諧波及無功電流問題,線損、中線及變壓器過熱、電表計(jì)量不準(zhǔn),甚至保護(hù)誤動(dòng)作等現(xiàn)象時(shí)有發(fā)生。傳統(tǒng)無源濾波及投切電容器補(bǔ)償盡管能夠解決上述問題,且成本較低,但無法實(shí)時(shí)連續(xù)調(diào)節(jié),存在過補(bǔ)償、無功倒送甚至誘發(fā)配電網(wǎng)諧振可能性[1-3]。
為**智能配電網(wǎng)終端用戶高品質(zhì)定制電力供應(yīng),隨著瞬時(shí)功率理論及電力電子器件的發(fā)展,取代無源濾波及電容器無功補(bǔ)償裝置,其主電路拓?fù)浣Y(jié)構(gòu)及設(shè)計(jì)、諧波電流檢測、補(bǔ)償方法、控制及調(diào)制策略,以及啟動(dòng)特性均是業(yè)界研究及工業(yè)應(yīng)用的持續(xù)熱點(diǎn)話題[2-6]。
由于如今智能配電網(wǎng)中電能質(zhì)量問題已經(jīng)不再是一個(gè)單一的問題,而是一個(gè)非常復(fù)雜的系統(tǒng)問題。如圖1所示,某公用設(shè)施配電系統(tǒng)中同時(shí)存在諧波電流、負(fù)載不平衡及功率因數(shù)較低等問題。電能質(zhì)量復(fù)合控制技術(shù)逐漸被學(xué)術(shù)界及工業(yè)界提上研究日程[7-8]。
圖1 實(shí)際配電網(wǎng)電能質(zhì)量問題
Fig. 1 Power quality issue in a real distributed grid
本文研究了智能配電網(wǎng)環(huán)境下,同時(shí)面對時(shí)變諧波電流、不平衡負(fù)載及無功問題,給出一種諧波、負(fù)序和無功電流復(fù)合補(bǔ)償策略,及其關(guān)鍵參數(shù)設(shè)計(jì)方法。相關(guān)仿真、實(shí)驗(yàn)驗(yàn)證及產(chǎn)品現(xiàn)場運(yùn)行實(shí)測結(jié)果驗(yàn)證了該控制策略的正確性及可行性。
APF-STATCOM電路結(jié)構(gòu)及工作機(jī)理
圖2 并聯(lián)APF-STATCOM框圖
Fig. 2 An APF-STATCOM diagram
如圖2所示,該并聯(lián)APF-STATCOM采用兩電平三相四橋臂電壓源逆變器拓?fù)?,其?*橋臂實(shí)現(xiàn)諧波及無功補(bǔ)償,*四橋臂獨(dú)立用于控制中線電流。這是由于三相四線制系統(tǒng)中,當(dāng)負(fù)載不平衡時(shí),中線往往流過較大零序電流,其不同于三相三線制系統(tǒng)。因此,增加與**橋臂解耦控制的*四橋臂提供零序電流通路。此時(shí)APF-STATCOM產(chǎn)生一個(gè)與負(fù)載電流iL,abc中諧波、基波負(fù)序和零序分量之和相反的補(bǔ)償電流iC,abc,使得電源電流iS,abc僅提供負(fù)載電流基波正序分量,確保源輸出對稱三相電流并提高功率因數(shù)。
其中中線電流分離檢測、鎖相環(huán)、諧波電流檢測、直流電壓控制、電流控制及PWM調(diào)制是實(shí)現(xiàn)高性能APF-STATCOM的關(guān)鍵。鎖相環(huán)、直流電壓控制等與三相三線制系統(tǒng)相同,在此不作詳細(xì)介紹。
關(guān)鍵問題分析
1. *四橋臂中線電流分離檢測及控制
考慮到不平衡的三相四線制電路中的負(fù)載電流iL,abc所包含的零序分量iN相等,均為
(1)
如圖2所示,此時(shí)中線電流采樣值iN,與中線零序電流分量補(bǔ)償指令iNref一并作為*四橋臂電流控制器輸入,通過PI調(diào)節(jié)器得到調(diào)制信號獲得*四橋臂開關(guān)信號。
同時(shí)有,
(2)
(3)
(4)
式中,僅含正序分量及負(fù)序分量,便于后續(xù)采用三相三線系統(tǒng)中ip-iq諧波電流檢測算法。
2. 諧波電流檢測
圖3 ?用d-q變換檢測諧波的原理圖
Fig. 3 The schematic diagram of the harmonics detecting method based on d-q rotating coordination transformation
傳統(tǒng)基于p-q瞬時(shí)無功功率理論檢測諧波電流方法受電壓畸變及不對稱影響較大,實(shí)際場合并不適用[9]。實(shí)際場合多采用加入鎖相環(huán)PLL電路的ip-iq瞬時(shí)無功功率理論檢測方法,具體如圖3所示,相關(guān)變換為
(5)
(6)
提取不含零序分量的電流 ,通過Park變換,將基波分量在d-q-0 坐標(biāo)中變換到0Hz處(或先經(jīng) 變換再經(jīng)dq變換亦可),用低通濾波器提取基波正序分量即可[5]。
圖2中直流電壓調(diào)節(jié)器輸出值生成部分有功電流指令,用于穩(wěn)定直流母線電壓并補(bǔ)償功率損耗部分。若為提高功率因數(shù),可以同時(shí)補(bǔ)償無功電流,此時(shí)基波負(fù)序無功電流指令值設(shè)定為0。最后用負(fù)載電流減去基波電流正序分量,即可得到補(bǔ)償負(fù)載電流中諧波分量和因負(fù)載不平衡導(dǎo)致的電流負(fù)序分量、零序分量的指令電流量以及無功電流正序分量的指令電流,實(shí)現(xiàn)APF-STATCOM功能。
3. 電流PR諧振控制器設(shè)計(jì)
由于APF-STATCOM跟蹤的電流指令是多種頻率正弦量的疊加信號,傳統(tǒng)SPWM調(diào)制采用PI控制必定存在穩(wěn)態(tài)誤差和相位偏移,補(bǔ)償效果不佳,往往采用電流滯環(huán)調(diào)制,但變頻調(diào)制不可避免帶來濾波器設(shè)計(jì)及噪聲控制問題[9]。
通過旋轉(zhuǎn)坐標(biāo)變換可以將正弦信號變?yōu)橹绷餍盘?,從而在新的坐?biāo)系下采用PI控制器。但在APF-STATCOM控制領(lǐng)域,必須在多個(gè)頻率下進(jìn)行坐標(biāo)變換,計(jì)算復(fù)雜,不利于實(shí)際應(yīng)用。近年來,針對正弦信號的提出的PR控制器,在可以避免旋轉(zhuǎn)坐標(biāo)變換,計(jì)算量大大降低的同時(shí),獲得與同步坐標(biāo)系下的PI控制器相同控制效果:能無穩(wěn)態(tài)誤差地跟蹤特定頻率的正弦信號,較重要的是可以對*頻率的諧波進(jìn)行有選擇地補(bǔ)償。
(7)
(8)
式中 為諧振頻率。
由式(7)可知,對直流系統(tǒng)而言,由于積分環(huán)節(jié)的存在,0 Hz處的增益較高,從而系統(tǒng)可以實(shí)現(xiàn)無靜差調(diào)節(jié);對于交流系統(tǒng),50Hz及其倍數(shù)次諧波,式(7)增益有限,式(8)由于諧振環(huán)節(jié)的引入,在相應(yīng)頻段有較高的增益。若跟蹤的目標(biāo)為基波 rad/s;若需補(bǔ)償較高幅值的5次諧波,則有 rad/s。通常補(bǔ)償諧波次數(shù)較高至20或50次,尤其是幅值較高的奇次諧波。因此有,
(9)
圖4所示為基波及三、五、七次諧波補(bǔ)償用PR諧振控制器波特圖,可以看出在相應(yīng)頻段電流控制器增益較高,有助于減小跟蹤誤差。
圖4 ?PR諧振控制器波特圖
Fig. 4 PR controller bode plots
仿真及實(shí)驗(yàn)驗(yàn)證
為驗(yàn)證所提出的諧波、負(fù)序及無功電流復(fù)合補(bǔ)償策略,本文在Matlab Simu
圖5所示以A相為例,表明補(bǔ)償后APF-STATCOM注入電流很好地抵消了負(fù)載電流的諧波電流,使得電網(wǎng)電流正弦化較好,實(shí)現(xiàn)了APF諧波補(bǔ)償功能;同時(shí)電網(wǎng)電流與電網(wǎng)電壓同頻同相,功率因數(shù)接近于1,實(shí)現(xiàn)了STATCOM無功補(bǔ)償功能。圖6給出三相補(bǔ)償結(jié)果,對稱三相電流波形驗(yàn)證其具有較好抑制不平衡負(fù)載能力。
圖5 A相補(bǔ)償后電壓電流波形(從上到下依次是電網(wǎng)電壓/V、電網(wǎng)電流/A、補(bǔ)償電流/A、負(fù)載電流/A,時(shí)間軸t/s)
Fig. 5 Phase A wave forms after compensation
圖6 補(bǔ)償后電網(wǎng)三相電壓電流波形(從上到下依次是三相電網(wǎng)電壓/V、三相電網(wǎng)電流/A,時(shí)間軸t/s)
Fig. 6 Three phase wave forms after compensation
圖7進(jìn)一步給出直流側(cè)母線電壓波形,可以看出APF-STATCOM在完成諧波補(bǔ)償后,母線電壓略有波動(dòng),但穩(wěn)定在750V設(shè)定值附近。
圖7 直流側(cè)母線電壓/V(時(shí)間軸t/s)
Fig. 7 Dc
圖8及圖9進(jìn)一步給出工業(yè)樣機(jī)內(nèi)部測試結(jié)果,受實(shí)驗(yàn)條件限制,此時(shí)負(fù)載僅為整流性非線性負(fù)載,故負(fù)載電流及補(bǔ)償電流與仿真有所區(qū)別,其主要體現(xiàn)了APF補(bǔ)償功能。圖10給出產(chǎn)品在現(xiàn)場投運(yùn)結(jié)果,與圖1相比,中性線電流由37A減小至5A,三相電流THD較大不**過3.4%,且對稱性較好,充分驗(yàn)證了APF-STATCOM復(fù)合補(bǔ)償功能。
圖8 A相及B相補(bǔ)償后網(wǎng)側(cè)電流及負(fù)載電流(從上到下依次是A相電壓、B相電流、A相負(fù)載電流、B相負(fù)載電流)
Fig. 9 Phase A &B grid & load current after compensation
圖9 A相補(bǔ)償后網(wǎng)側(cè)電流、發(fā)出反向諧波電流及負(fù)載電流
Fig. 9 Phase A grid, inverse harmonic current & load current after compensation
圖10 實(shí)際現(xiàn)場APF-STATCOM補(bǔ)償后結(jié)果
Fig. 10 APF-STATCOM Compensation effects in practice
結(jié)論語
基于電能質(zhì)量復(fù)合控制思想,針對智能配電網(wǎng)中諧波電流、負(fù)載不平衡、功率因數(shù)較低問題,提出一種諧波、負(fù)序及無功電流復(fù)合補(bǔ)償策略。
仿真、工程樣機(jī)試驗(yàn)及現(xiàn)場運(yùn)行結(jié)果驗(yàn)證了基于該策略所實(shí)現(xiàn)的APF-STATCOM復(fù)合補(bǔ)償功能。
文章來源:《電氣應(yīng)用》2014年 *6期
參考文獻(xiàn)
1.國家技術(shù)監(jiān)督局.中國國家標(biāo)準(zhǔn)GB/T 14549-93電能質(zhì)量公用電網(wǎng)諧波[S].北京:中標(biāo)準(zhǔn)準(zhǔn)出版社,1994.
2.赤木泰文(Hirofumi Akagi)等(徐政 譯).瞬時(shí)功率理論及其在電力調(diào)節(jié)中的應(yīng)用[J].北京:機(jī)械工業(yè)出版社,2009.
3.王兆安,楊君,劉進(jìn)軍.諧波抑制和無功功率補(bǔ)償。機(jī)械工業(yè)出版社,1998.
4.馬莉,周景海,呂征宇,錢照明.一種基于dq 變換的改進(jìn)型諧波檢測方案的研究[J].中國電機(jī)工程學(xué)報(bào),2000,20(10):55-63.
Ma Li,Zhou Jinghai,LüZhengyu,Qian Zhaoming. An improved harmonic detecting approach based on dq rotating coordination transformation[J].Proceedings of the CSEE,2000,20(10):55-63(in Chinese).
Zeliang Shu, Yuhua Guo, and Jisan Lian. Steady-state and dynamic study of active power filter with efficient FPGA-based control algorithm [J].IEEE Transactions on Industrial Electronics,2008,55(4):1527- 1536.
5.趙國鵬,林少伯,韓民曉.基于補(bǔ)償特性的并聯(lián)型有源電力濾波器直流側(cè)電壓取值分析[J].電力系統(tǒng)自動(dòng)化,2012,36(14):83-87.
Zhao Guopeng,Lin Shaobo,Han Minxiao.Design of voltage in DC
6.單任仲.并聯(lián)型復(fù)合電能質(zhì)量擾動(dòng)及補(bǔ)償?shù)目刂品椒ㄅc實(shí)現(xiàn) [D].博士學(xué)位論文,北京:華北電力大學(xué),2010.
7.劉海波,毛承雄,陸繼明,王丹.四橋臂三相四線制并聯(lián)型APF—STATCOM [J].電力系統(tǒng)保護(hù)與控制,2010,38(16):11-17.
Liu Haibo,Mao Chengxiong, Lu Jiming,Wang Dan.Three-phase four-wire shunt APF-STATCOM using a four-leg converter [J].Power System Protection and Control,2010,38(16):11-17 (in Chinese).
8.曹武.諧波獨(dú)立補(bǔ)償有源濾器關(guān)鍵技術(shù)研究[D].碩士學(xué)位論文,南京:東南大學(xué),2011.
詞條
詞條說明
淺談智能電氣火災(zāi)監(jiān)控在建筑*中的應(yīng)用及產(chǎn)品選型
摘要:在開展*工作時(shí),為充分發(fā)揮電氣火災(zāi)監(jiān)控系統(tǒng)的運(yùn)行優(yōu)勢與作用,應(yīng)靈活運(yùn)用相關(guān)探測器技術(shù),如剩余電流式、測溫式、故障電弧等。為實(shí)現(xiàn)電氣火災(zāi)監(jiān)控系統(tǒng)運(yùn)行的預(yù)期目標(biāo),在系統(tǒng)設(shè)計(jì)時(shí),可以下設(shè)計(jì)要點(diǎn),如組成方式設(shè)計(jì)、探測器位置設(shè)計(jì)、主機(jī)位置設(shè)計(jì)、報(bào)警閾值設(shè)計(jì)、監(jiān)控系統(tǒng)的運(yùn)行等。關(guān)鍵詞:電氣火災(zāi)監(jiān)控系統(tǒng);實(shí)際應(yīng)用;關(guān)鍵技術(shù);系統(tǒng)設(shè)計(jì)0 引言為筑牢建筑工程運(yùn)行基石,有效規(guī)避電氣火災(zāi)事故,要高度重視建筑*
淺談配電室在線監(jiān)控系統(tǒng)設(shè)計(jì)與工作原理
摘要:為了及時(shí)發(fā)現(xiàn)配電室滲漏水、變壓器溫度過高、室內(nèi)進(jìn)入非工作人員等問題,本文結(jié)合嵌入式技術(shù)設(shè)計(jì)配電室在線監(jiān)控系統(tǒng)。在線監(jiān)控系統(tǒng)由在線監(jiān)控主機(jī)、采集子節(jié)點(diǎn)、上位機(jī)系統(tǒng)組成,在線監(jiān)控器可以實(shí)時(shí)對配電室內(nèi)的濕度、變壓器溫度、室內(nèi)異動(dòng)情況進(jìn)行監(jiān)測,及時(shí)發(fā)現(xiàn)相關(guān)問題。通過對滲漏水配電室進(jìn)行監(jiān)測試驗(yàn),均能及時(shí)發(fā)現(xiàn)問題并發(fā)送至上位機(jī)軟件進(jìn)行報(bào)警,證明了該系統(tǒng)的可靠性。關(guān)鍵詞:配電室;在線監(jiān)測器;上位機(jī)&nbs
淺談綜合管廊智能互聯(lián)運(yùn)營及配電監(jiān)控系統(tǒng)研究
摘要:分析地下綜合管廊智能互聯(lián)運(yùn)營監(jiān)控系統(tǒng)的需求,構(gòu)建智能互聯(lián)監(jiān)控系統(tǒng)架構(gòu),包括環(huán)境與設(shè)備監(jiān)控系統(tǒng)、監(jiān)控系統(tǒng)、通信系統(tǒng)和智慧管廊綜合監(jiān)控平臺四個(gè)子系統(tǒng),為綜合管廊智能化管理提供參考。關(guān)鍵詞:地下綜合管廊;智能互聯(lián);運(yùn)營監(jiān)控系統(tǒng);BIM;物聯(lián)網(wǎng)1 引言近年來,地下綜合管廊已成為建設(shè)現(xiàn)代化“城市”、“智慧城市”的重要環(huán)節(jié)。在綜合管廊運(yùn)營過程中,由于管廊位于地下呈封閉性,不確定因素較多,受工程地質(zhì)和水文
淺談高壓配電柜溫度在線監(jiān)測系統(tǒng)的設(shè)計(jì)及選型
摘要:高壓配電柜是電力系統(tǒng)的關(guān)鍵電能分配節(jié)點(diǎn),保證其運(yùn)行的穩(wěn)定可靠具有重要意義。文章綜合運(yùn)用了470MHz無線測溫、無線傳輸?shù)燃夹g(shù)手段,設(shè)計(jì)了一套高壓配電柜溫度監(jiān)測系統(tǒng)。應(yīng)用結(jié)果表明,本系統(tǒng)運(yùn)行穩(wěn)定可靠,數(shù)據(jù)準(zhǔn)確,預(yù)警及時(shí),滿足一般電力系統(tǒng)的應(yīng)用要求。關(guān)鍵詞:高壓;配電柜;溫度監(jiān)測一、引言? ? ? ?隨著電氣自動(dòng)化技術(shù)的普遍應(yīng)用供配電系統(tǒng)的綜合性能越來越受
公司名: 安科瑞電子商務(wù)(上海)有限公司
聯(lián)系人: 王孟春
電 話: 021-69153586
手 機(jī): 13524471462
微 信: 13524471462
地 址: 上海嘉定馬陸鎮(zhèn)育綠路253號
郵 編:
網(wǎng) 址: acrel1001.cn.b2b168.com
公司名: 安科瑞電子商務(wù)(上海)有限公司
聯(lián)系人: 王孟春
手 機(jī): 13524471462
電 話: 021-69153586
地 址: 上海嘉定馬陸鎮(zhèn)育綠路253號
郵 編:
網(wǎng) 址: acrel1001.cn.b2b168.com